Basic wind speed, V, from the BNBC basic wind speed map — Figure 6.2.1; wind is considered from any horizontal direction — Section 2.4.4.
Importance factor, I, from Table 6.2.9 — Section 2.4.5.
Terrain exposure category and velocity pressure exposure coefficient, Kz, from Sections 2.4.6.2–2.4.6.6 and Tables 6.2.10–6.2.11.
Wind directionality factor, Kd, from Table 6.2.12 — Section 2.4.4.3.
Topographic factor, Kzt, from Section 2.4.7; use 1.0 where the specified topographic conditions do not apply.
Gust-effect factor, G, from Section 2.4.8. For rigid structures, BNBC permits 0.85 or calculation using the stated procedure.
Building enclosure classification and internal pressure coefficient, Cpi, from Sections 2.4.9–2.4.10.1 and Figure 6.2.5.
2. Velocity pressure
Velocity pressure at height z is calculated in SI units using Equation 6.2.17, Section 2.4.9.5:
qz = 0.000613 Kz Kzt Kd I V² (kN/m²)
V is in m/s. Kz is evaluated at the relevant height; for the roof-level pressure use the mean roof height, h.
3. External pressure coefficients — walls and flat roof
For the enclosed/partially enclosed building MWFRS procedure in this application, external pressure coefficients are taken from Figure 6.2.6 — Section 2.4.10.2.
Surface
BNBC coefficient
Reference velocity pressure
Windward wall
Cp = +0.8
qz
Leeward wall
Based on L/B; interpolate between tabulated values
qh
Side wall
Cp = −0.7
qh
Flat roof (θ < 10°)
From roof pressure coefficient table in Figure 6.2.6; based on h/L
qh
For intermediate L/B and h/L values, BNBC permits linear interpolation as stated in the notes to Figure 6.2.6. This application is limited to the flat-roof case represented by its existing geometry and roof-zone diagram.
4. Net design pressure
For rigid buildings of all heights, MWFRS design pressure is determined using Equation 6.2.19, Section 2.4.11.2:
p = q (G Cp) − q (G Cpi) (kN/m²)
Windward wall external pressure uses qz at the relevant height; leeward wall, side-wall and roof pressures use qh at mean roof height. External and internal pressures are combined algebraically for the critical condition.
5. Minimum design wind load
The minimum MWFRS design load check is presented separately in accordance with Section 2.4.2.1. It is not substituted for the calculated pressure distribution; the applicable minimum load case must also be considered.
This reference describes the provisions implemented in this calculator. It is not a substitute for checking the complete BNBC 2020, project-specific conditions, and all applicable load combinations.
BNBC 2020 Sec. 2.4.2.1 Minimum Design Wind Load Check: MWFRS design load ≥ 0.50 kN/m² multiplied by the building area projected onto a vertical plane normal to the wind; apply as a separate minimum load case.
Check Required
Top-Down Plan View & Roof Zones
Wind Parallel to X • Windward Width B = 80 ft, Length L = 120 ft
PLAN VIEW
Windward (+ Inward) Leeward (− Suction) Side Walls (− Suction)
Sign: (+) Toward Surface, (−) Away
Elevation Cross-Section & Pressure Profile
Vertical Kz Gradient (15 ft Cutoff) & Flat Roof Uplift Zones
ELEVATION
Internal Pressure (GCpi) Roof Uplift (Primary Cp)
Constant qz below z = 15.0 ft
Vertical Velocity & Wall Pressure Profile
Elevation z vs. Velocity Pressure qz & Net Windward Pressure pw
Eq. 6.2.17
BNBC 2020 Intermediate Parameter Breakdown
Transparent step-by-step variables for engineering verification
AUDIT TRAIL
Parameter
Symbol
Value
BNBC 2020 Ref.
Flat Roof Design Wind Pressures by Zone (θ = 0°)
Evaluated at qh using interpolated Cp from BNBC 2020 Fig. 6.2.6 (Wind Parallel to Ridge / Flat Roof)
h/L = 0.38 (≤ 0.50)
Roof Zone
Distance from Windward Edge
Primary Cp,1
Net Pressure p1 (kN/m²)
Secondary Cp,2
Net Pressure p2 (kN/m²)
BNBC Note
Story-by-Story Wall Design Wind Pressure Schedule
Equation 6.2.19: p = q · G · Cp − qh · (±GCpi) • Windward evaluated at qz; Leeward & Side Walls evaluated at qh